KONNEKTING Protocol Specification 0x01

From KONNEKTING Wiki
Revision as of 16:09, 31 July 2018 by Konnekting (talk | contribs)
Jump to navigation Jump to search

Workflow

The following describes the workflow for programming a KONNEKTING device. The diagrams show the required actions the programming device (f.i. KONNEKTING Suite) needs to do in order to program a KONNEKTING device.

Start Programming Mode

Before the programming can start, the device needs to be in "programming mode" (short: ProgMode). The following diagram describes the two possible ways to achive ProgMode.

drawio: Protocol0x01WorkflowProgMode

Do Programming

After ProgMode has been achived, it's time to do the actual device programming.

drawio: Protocol0x01WorkflowTables

The parts for "Program CommObjects" and "Program Parameters" are optional an depend on what the user want to program. So you can skip or include them, as you like.

Working with files

This is about working with files, means transfering files to the device, including firmware upgrade

todo ...

Device Memory Layout

The device's memory is divided in multiple sections:

drawio: Protocol0x01MemoryLayout

System Table

  • Total table size in bytes: 32 bytes, fixed
Table Byte Index Description
0 Device Flags, see below
1 IndividualAddress LO
2 IndividualAddress HI
3..31 0xFF, unused

Device Flags

b7 ist the left most bit, b0 is the right most bit.

bit hex mask Description
b7 0x80 Factory Flag:
  • 1 = factory settings
  • 0 = stored settings
b6..b0 n/a unused

GroupAddress Table

  • Total table size in bytes: 1+(n*2) bytes, where n = GroupAddress limit, see #System_Type
Table Byte Index Description
0 number of filled entries in table
1 GroupAddress 0 LO
2 GroupAddress 0 HI
3 GroupAddress 1 LO
4 GroupAddress 1 HI
5 GroupAddress 2 LO
6 GroupAddress 2 HI
... ...

Association Table

  • Total table size in bytes: 1+(n*2) bytes, where n = GA-CommObj relation limit, see #System_Type
Table Byte Index Description
0 number of filled entries in GA<->CommObj relations table
1 GroupAddress ID Nr.1
2 CommObj ID Nr.1
3 GroupAddress ID Nr.2
4 CommObj ID Nr.2
5 GroupAddress ID Nr.3
6 CommObj ID Nr.3
... ...

CommObjectTable

  • Total table size in bytes: 1+(n) bytes, where n = CommObjects limit, see #System_Type
Table Byte Index Description
0 number of existing CommObjects
1 config byte (see below) of CommObject ID 0
2 config byte of CommObject ID 1
3 config byte of CommObject ID 2
... ...

CommObject config byte

b7 ist the left most bit, b0 is the right most bit.

bit hex mask Description
b7 0x80 TODO
b6..b0 n/a unused

Parameter Table

  • Total table size in bytes: depends on actual by device provided parameters
Table Byte Index Description
0 ...
1 ...
2 ...
3 ...
... ...

User Space

This is the space where user data can be stored. The KONNEKTING Device Library provides an API to query the start address for this user space in memory.

Message Types for Protocol-Version 0x01

--- DRAFT ---
This is the second protocol version (version=0x01), starting with 1.0.0 beta5
--- DRAFT ---

0x00 Acknowledge

  • Message Name: Acknowledge
  • Message-Type-ID: 0 dec / 0x00 hex
  • Direction: Device -> Suite
  • Expected Response: n/a
  • Description: Sent by device as answer to most WRITE messages
  • Requires Programming Mode: n/a
Byte no# Description
2 Acknowledge Type
3 Error Code
4..13 0xFF, unused

Acknowledge Type

hex Description
0x00 ACK
0xFF NACK

Error Code

hex Description
0x00 no error / no error code available
0x01 PropertyPage not available/invalid
0x02 Memory adress not available/invalid

0x01 PropertyPageRead

  • Message Name: PropertyPageRead
  • Message-Type-ID: 1 dec / 0x01 hex
  • Direction: Suite -> Device
  • Expected Response: #0x02 PropertyPageResponse
  • Description: Read one page of property data
  • Requires Programming Mode: no
Byte no# Description
2 IndividualAddress LO
3 IndividualAddress HI
4 property page num, 0x00..0xFF, see #Property Pages for more details
4..13 0xFF, unused

Property Pages

0x00 Device Info

  • Property Page Number: 0 dec / 0x00 hex
  • Property Page Name: Device Information
Byte no# Description
2 Manufacturer-ID LO
3 Manufacturer-ID HI
4 Device-ID
5 RevisionID
6 Device Flags, see below
7 System Type, see below
8..13 0xFF, unused
Device Flags

b7 ist the left most bit, b0 is the right most bit.

bit hex mask Description
b7 0x80 Factory Flag:
  • 1 = factory settings
  • 0 = stored settings
b6..b0 n/a unused
System Type
hex Name Description
0x00 System 1
Default
Up to:
  • 256 GAs
  • 256 GA-ComObj relations
  • 256 ComObjects
  • 256 Parameters
0x01 System 2
Simple
Up to:
  • 128 GAs
  • 128 GA-ComObj relations
  • 128 ComObjects
  • 128 Parameters
0x02 System 3
Extended
DRAFT
Up to:
  • 65535 GAs (32*8*256)
  • 65535 GA-ComObj relations
  • 65535 ComObjects
  • 65535 Parameters

GAs = Unique GroupAddresses
GA-ComObj relations = Assignments of GAs to ComObjects
ComObjects = Number of ComObjects
Parameters = Number of Paramaters

0x01 Table Addresses

  • Property Page Number: 1 dec / 0x01 hex
  • Property Page Name: Information about table addresses
Byte no# Description
2 systemtable LO
3 systemtable HI
4 addresstable LO
5 addresstable HI
6 associationtable LO
7 associationtable HI
8 comobjecttable LO
9 comobjecttable HI
10 parametertable LO
11 parametertable HI
12..13 0xFF, unused

0x02 PropertyPageResponse

  • Message Name: PropertyPageResponse
  • Message-Type-ID: 2 dec / 0x02 hex
  • Direction: Device -> Suite
  • Expected Response: n/a
  • Description: One page of property data
  • Requires Programming Mode: no
Byte no# Description
2..13 12 bytes of property page data, see #Property Pages for more details

0x09 Restart

  • Message Name: Restart
  • Message-Type-ID: 9 dec / 0x09 hex
  • Direction: Suite -> Device
  • Expected Response: #0x00 Acknowledge
  • Description: Restart device (device reboot, no memory reset)
  • Requires Programming Mode: no
Byte no# Description
2 IndividualAddress LO
3 IndividualAddress HI
4..13 0xFF, unused


0x0A ProgrammingModeWrite

  • Message Name: ProgrammingModeWrite
  • Message-Type-ID: 10 dec / 0x0A hex
  • Direction: Suite -> Device
  • Expected Response: #0x00 Acknowledge
  • Description: Sets/Unsets Programming-Mode for device with given individual address. Device will respond with a "Acknowledge" message.
  • Requires Programming Mode: no
Byte no# Description
2 IndividualAddress LO
3 IndividualAddress HI
4 Mode:

0x00 = OFF
0x01 = ON

5..13 0xFF, unused


0x0B ProgrammingModeRead

  • Message Name: ProgrammingModeRead
  • Message-Type-ID: 11 dec / 0x10 hex
  • Direction: Suite -> Device
  • Expected Response: #0x0C ProgrammingModeResponse
  • Description: Reads current programming mode of all listening devices. If more than one device is in programming-mode, you will get more then one #0x0C ProgrammingModeResponse messages.
  • Requires Programming Mode: no
Byte no# Description
2..13 0xFF, unused

0x0C ProgrammingModeResponse

  • Message Name: ProgrammingModeResponse
  • Message-Type-ID: 12 dec / 0x11 hex
  • Direction: Device -> Suite
  • Expected Response: n/a
  • Description: Response to ProgrammingModeRead message.
  • Requires Programming Mode: n/a
Byte no# Description
2 IndividualAddress LO
3 IndividualAddress HI
4..13 0xFF, unused


0x1E MemoryWrite

  • Message Name: MemoryWrite
  • Message-Type-ID: ?? dec / 0x?? hex
  • Direction: Suite -> Device
  • Expected Response: #0x00 Acknowledge
  • Description: Write data to device memory
  • Requires Programming Mode: yes
Byte no# Description
2 Count: Number of bytes to write to memory, starting at "Address"
3 Address uint16[1] LO
4 Address uint16[0] HI
5..13 1..9 bytes of Data, depends on "Count". Remaining bytes: 0xFF

0x1F MemoryRead

  • Message Name: MemoryRead
  • Message-Type-ID: ?? dec / 0x?? hex
  • Direction: Suite -> Device
  • Expected Response: #0x20 MemoryResponse
  • Description: Reads data from device memory
  • Requires Programming Mode: yes
Byte no# Description
2 Count: Number of bytes to read from address. Range 1..9
3 Address LO
4 Address HI
5..13 0xFF, unused

Memory Tables

With help of #0x1F MemoryRead and #0x1E MemoryWrite one can access the device's memory (EEPROM, flash, ...). The memory stores different tables for different usage. As both messages access memory by memory address, one has to know at which address which table starts. To get the start addresses of all tables, see #0x01 PropertyPageRead and #0x01 Table Addresses.

0x20 MemoryResponse

  • Message Name: MemoryResponse
  • Message-Type-ID: ?? dec / 0x?? hex
  • Direction: Device -> Suite
  • Expected Response: n/a
  • Description: Response to MemoryRead
  • Requires Programming Mode: yes
Byte no# Description
2 Count: Number of bytes that have been read from address
3 Address LO
4 Address HI
5..13 1..9 bytes of Data, depends on "Count". Remaining bytes: 0xFF


0x28 DataPrepare

  • Message Name: DataPrepare
  • Message-Type-ID: 40 dec / 0x28 hex
  • Direction: Suite -> Device
  • Expected Response: #0x00 Acknowledge
  • Description: prepare update
  • Requires Programming Mode: yes
Byte no# Description
2 Data Type, see below
3 Data ID
unique identifier for the data
4 size of data uint32[0]
5 size of data uint32[1]
6 size of data uint32[2]
7 size of data uint32[3]
8..13 unused, 0xFF

Data Type

hex Name Data ID range Description
0x00 UPDATE always 0x00 Firmware update for KONNEKTING device
0x01 DATA 0x00..0xFF f.i. additional configuration, images, sounds, ...

0x29 DataWrite

  • Message Name: DataWrite
  • Message-Type-ID: 41 dec / 0x29 hex
  • Direction: Suite -> Device
  • Expected Response: #0x00 Acknowledge
  • Description: Writing data
  • Requires Programming Mode: yes
Byte no# Description
2 Count[1]: 1..11 bytes
3..13 1..11 bytes of Data, depends on "Count". Remaining bytes: 0xFF

Notes:

  1. required to determin the end of data in last DataWrite message

0x2A DataFinish

  • Message Name: DataFinish
  • Message-Type-ID: 42 dec / 0x2A hex
  • Description: finish writing data
  • Requires Programming Mode: yes
Byte no# Description
2 CRC32[0] [1]
3 CRC32[1]
4 CRC32[2]
5 CRC32[3]
6..13 unused, 0xFF

Notes:

0x2B DataRemove

  • Message Name: DataRemove
  • Message-Type-ID: 43 dec / 0x2B hex
  • Direction: Suite -> Device
  • Expected Response: #0x00 Acknowledge
  • Description: remove previously stored data
  • Requires Programming Mode: yes
Byte no# Description
2 Data Type
0x01..0xFF[1]
3 Data ID
unique identifier for the data
4..13 unused, 0xFF

Notes:

  1. 0x00 is reserved for UPDATE