The programming protocol uses group telegrams with the mostly unused group address 15/7/255. Those telegrams use DPT 60000.000, which is unreserved for manufacturer specific extensions. The used Property Data Type is PDT_GENERIC_14, which is 14 bytes of raw data.

!!! It's required that no other device is using this address. Otherwise it may conflict with KONNEKTING Devices !!!

Byte no#: 0 1 2 ... 13
Used for: Header, 2 bytes Body, 12 Bytes
Description: Protocolversion Message-Type-ID depends on Message-Type-ID
Range: 0x00..0xFF 0x00..0xFF

There are several message types for all kind of purposes. As we have one byte for the Message-Type-ID, we have up to 256 possible messages. That should be enough for our purposes. Same for version: Up to 256 versions should be enough for the near future.