KONNEKTING Protocol Specification 0x00
Revision as of 17:04, 5 March 2018 by Konnekting (talk | contribs) (Created page with "= Message Types for Protocol-Version 0x00 = This is the first protocol version. == 0x00 Acknowledge == * '''Message Name:''' Acknowledge * '''MsgID:''' 0 dec / 0x00 hex...")
Message Types for Protocol-Version 0x00
This is the first protocol version.
0x00 Acknowledge
- Message Name: Acknowledge
- MsgID: 0 dec / 0x00 hex
- Description: Acknowledge a previous received WRITE message
- Requires Programming Mode: n/a
Byte no# | Description |
---|---|
2 | Acknowledge type: 0x00: ACK |
3 | Error-Code (only NACK): 0x00: no error / no error code available |
4 | Affected index (only NACK): 0x00..0xFE: errornous index |
5..13 | 0x00, unused |
0x01 ReadDeviceInfo
- Message Name: ReadDeviceInfo
- MsgID: 1 dec / 0x01 hex
- Description: Initiates reading general device information
- Requires Programming Mode: no
Byte no# | Description |
---|---|
2 | IndividualAddress HI |
3 | IndividualAddress LO |
4..13 | 0x00, unused |
0x02 AnswerDeviceInfo
- Message Name: AnswerDeviceInfo
- MsgID: 2 dec / 0x02 hex
- Description: Answers a ReadDeviceInfo message
- Requires Programming Mode: n/a
Byte no# | Description |
---|---|
2 | Manufacturer-ID HI |
3 | Manufacturer-ID LO |
4 | Device-ID |
5 | RevisionID |
6 | Device Flags Flag masks: |
7 | IndividualAddress HI |
8 | IndividualAddress LO |
9..13 | 0x00, unused |
0x09 Restart
- Message Name: Restart
- MsgID: 9 dec / 0x09 hex
- Description: Restart device (device reboot, no memory reset)
- Requires Programming Mode: no
Byte no# | Description |
---|---|
2 | IndividualAddress HI |
3 | IndividualAddress LO |
4..13 | 0x00, unused |
0x0A WriteProgrammingMode
- Message Name: WriteProgrammingMode
- MsgID: 10 dec / 0x0A hex
- Description: Sets/Unsets Programming-Mode for device with given individual address. Device will respond with a "Acknowledge" message.
- Requires Programming Mode: no
Byte no# | Description |
---|---|
2 | IndividualAddress HI |
3 | IndividualAddress LO |
4 | Mode: 0x00 = OFF |
5..13 | 0x00, unused |
0x0B ReadProgrammingMode
- Message Name: ReadProgrammingMode
- MsgID: 11 dec / 0x10 hex
- Description: Reads current programming mode of all listening devices. If more than one device is in programming-mode, you will get more then one AnswerProgrammingMode messages.
- Requires Programming Mode: no
Byte no# | Description |
---|---|
2..13 | 0x00, unused |
0x0C AnswerProgrammingMode
- Message Name: AnswerProgrammingMode
- MsgID: 12 dec / 0x11 hex
- Description: Answers a ReadDeviceInfo message with the device's individual address.
- Requires Programming Mode: n/a
Byte no# | Description |
---|---|
2 | IndividualAddress HI |
3 | IndividualAddress LO |
4..13 | 0x00, unused |
0x14 WriteIndividualAddress
- Message Name: WriteProgrammingMode
- MsgID: 20 dec / 0x14 hex
- Description: Writes the individual address the device should use. Device will respond with a "Acknowledge" message.
- Requires Programming Mode: yes
Byte no# | Description |
---|---|
2 | IndividualAddress HI |
3 | IndividualAddress LO |
4..13 | 0x00, unused |
0x15 ReadIndividualAddress
- Message Name: ReadIndividualAddress
- MsgID: 21 dec / 0x15 hex
- Description: Each device in programming mode will respond with its individual address
- Requires Programming Mode: yes
Byte no# | Description |
---|---|
2..13 | 0x00, unused |
0x16 AnswerIndividualAddress
- Message Name: AnswerIndividualAddress
- MsgID: 22 dec / 0x16 hex
- Description: Answers a ReadIndividualAddress message with the device's individual address.
- Requires Programming Mode: n/a
Byte no# | Description |
---|---|
2 | IndividualAddress HI |
3 | IndividualAddress LO |
4..13 | 0x00, unused |
0x1E WriteParameter
- Message Name: WriteParameter
- MsgID: 30 dec / 0x1E hex
- Description: Writes a value for a specific parameter. Device will respond with a "Acknowledge" message.
- Requires Programming Mode: yes
Byte no# | Description |
---|---|
2 | Parameter ID |
3..13 | parameter value, up 10 11 bytes. Data depends on parameter type |
0x1F ReadParameter
- Message Name: ReadParameter
- MsgID: 31 dec / 0x1F hex
- Description: Reads a value for a specific parameter
- Requires Programming Mode: yes
Byte no# | Description |
---|---|
2 | Parameter ID |
3..13 | 0x00, unused |
0x20 AnswerParameter
- Message Name: AnswerParameter
- MsgID: 32 dec / 0x20 hex
- Description: Answers a ReadDeviceInfo message with the device's individual address.
- Requires Programming Mode: n/a
Byte no# | Description |
---|---|
2 | Parameter ID |
3..13 | parameter value, up 10 11 bytes. Data depends on parameter type |
0x28 WriteCommObject
- Message Name: WriteCommObject
- MsgID: 40 dec / 0x28 hex
- Description: Writes a GA for a specific CommObjects. Device will respond with a "Acknowledge" message.
- Requires Programming Mode: yes
Byte no# | Description |
---|---|
2 | CommObject ID |
3 | GA HI |
4 | GA LO |
5 | Settings |
6..13 | parameter value, up 10 11 bytes. Data depends on parameter type |
0x29 ReadCommObject
- Message Name: ReadCommObject
- MsgID: 41 dec / 0x29 hex
- Description: Reads up to 3 GAs for a specific CommObjects.
- Requires Programming Mode: no
Byte no# | Description |
---|---|
2 | CommObject ID |
3..13 | parameter value, up 10 11 bytes. Data depends on parameter type |
0x2A AnswerCommObject
- Message Name: AnswerCommObject
- MsgID: 42 dec / 0x2A hex
- Description: Answers read request for a specific CommObjects.
- Requires Programming Mode: n/a
Byte no# | Description |
---|---|
2 | CommObject ID |
3 | GA HI |
4 | GA LO |
5 | Settings |
6..13 | 0x00, unused |