KONNEKTING Protocol Specification
The programming protocol uses group telegrams with the mostly unused group address 15/7/255. Those telegrams use DPT 60000.000, which is reserved for manufacturer specific custom extensions. The used Property Data Type is PDT_GENERIC_14, which is 14 bytes of raw data.
!!! It's required that no other device is using this address. Otherwise it may conflict with KONNEKTING Devices and programming your devices may fail !!!
Byte no#: | 0 | 1 | 2 | ... | 13 |
---|---|---|---|---|---|
Used for: | Header, 2 bytes | Body, 12 Bytes | |||
Description: | Protocolversion | Message-Type-ID | depends on Message-Type-ID | ||
Range: | 0x00..0xFF | 0x00..0xFF |
There are several message types for all kind of purposes. As we have one byte for the Message-Type-ID, we have up to 256 possible messages. That should be enough for our purposes. Same for version: Up to 256 versions should be enough for the near future.
Glossary
- LO low byte, right most byte, f.i. b[0] of 2-byte-array (little endian byte order)
- HI high byte, left most byte, f.i. b[1] of 2-byte-array (little endian byte order)
- GA group address, 1/2/3
- IA or individual address aka. PA or physical address, 1.2.3
Protocol Versions